The combined transformer for wind (solar) power generation is a stationary transformer equipment which integrates the booster transformer body, switchgear, high-voltage current-limiting fuse, tap switch and corresponding auxiliary equipment. For the particularity of wind (solar) power generation, to provide users with reasonable solutions, it is an ideal supporting step-up transformer for wind (solar) generator sets.
1. Voltage
System voltage: 35kV(36.75kV, 38.5kV)
Maximum operating voltage at the high voltage side: 40.5kV
Rated voltage at the low voltage side: 0.69kV
2. Rated Frequency: 50Hz
3. Rated Insulation Level
Industrial frequency withstand voltage of the high-voltage switch: 95kV
Industrial frequency withstand voltage of the transformer body 85kV
Impulse withstand voltage peak value: 200kV
Industrial frequency withstand voltage at the industrial frequency withstand voltage of the transformer: 5kV
4. Number of Phases: three-phase
5. Cabinet Protection Level: oil tank IP68, high and low-voltage chamber IP54, after the high-voltage chamber door is opened IP3X
Transformer Capacity (kVA) | High-voltage Combination and Tapping Range | Connection Group Grade | No-load Loss kW | Load Loss kW | Impedance % | ||
High-voltage V | Tapping Range % | Low-voltage kV |
|
|
|
| |
1600 | 35 | ±2×2.5 | 0.69 | Dyn11 | According to customers’ requirements | According to customers’ requirements | 6.5 |
2150 | |||||||
2280 |
It has the advantages of strong completeness, easy installation, short construction cycle, low operating expense, high structure strength, and high anti-corrosion performance, etc.
Character '罒' Structure
Capacity (kVA) | L (mm) | W (mm) | H (mm) |
1600 | 3450 | 2450 | 2150 |
2150 | 3500 | 2500 | 2200 |
2280 | 3550 | 2550 | 2250 |
Character '品' Structure
Capacity (kVA) | L (mm) | W (mm) | H (mm) |
1600 | 3350 | 2750 | 2150 |
2150 | 3400 | 2800 | 2200 |
2280 | 3450 | 2850 | 2250 |
1. The elevation shall not exceed 1,000m;
2. Ambient Temperature: Maximum air temperature of 45℃/113℉
Minimum air temperature of -25℃/-13℉
3. Relative Humidity: daily relative humidity shall not exceed 95%, and the monthly average shall not exceed 90%;
4. The outdoor wind speed shall not exceed 35m/s;
5. The ground inclination shall not exceed 3°;
6. The waveform of the supply voltage is similar to sine wave, and the three-phase supply voltage is approximately symmetrical;
7. Places free of explosion hazard, fire, serious dirtiness, chemical corrosion and violent vibration.